UL 1077 Overcurrent Terminology: Trip-Free & Trip-Free, Cycling

Today’s article continues our review of UL1077 overcurrent terminology by explaining the differences between supplementary protectors that are identified as either “Trip Free” or “Trip Free, Cycling”.

According to UL1077:

A “Trip-Free” supplementary protector is, “a protector designed so that the contacts cannot be held in the closed position by the operating means during trip command conditions.”  In other words, a “Trip-Free” device has the ability to automatically open a circuit in a fault situation, even though its actuator is physically held in the “on” position.  This could also be thought of as “Trip-Free, Non-Cycling” (in contrast to the “Trip-Free-Cycling” described below) by UL1077’s requirements, as the contacts should remain in the open position until the actuator is released and reset.

A “Trip-Free, Cycling” supplementary protector (aka, Cycling Trip-Free) is, “a protector designed so that the contacts cannot be held in the closed position by the operating means during trip command conditions, but will reclose when the closing command is maintained.  The protector will continue to close momentarily and repeatedly as long as the close command is maintained by the operating means during trip-command conditions.” In other words, a “Trip-Free, Cycling” device, with its actuator held in the “on” position, will act as an automatic-reset protective device as long as the fault condition is present, cycling repeatedly between opened and closed circuit conditions until such time as the fault is removed or the device fails.

While the mechanisms required of “Trip-Free” devices make them generally more expensive than “Trip-Free, Cycling” types, due to various design issues associated with the end product, one type of mechanism may be preferable over the other.  Despite the designer’s preference, close attention should be paid to the agency standards applicable to the end product.   Dictates within specific standards may mandate the use of one type of operating mechanism over the other.

Tags: UL1077 Devices