Abstract Low voltage (300 Volts and below) network overcurrent
protection consists of a series connection of circuit protectors that both
detect the presence and interrupt the flow of circuit overcurrents. Overcurrent
circuit protectors operate in a cascading manner, with each designed to
function at a set level and duration of overcurrent flow. Standard low voltage protection devices
are: fuses, thermal circuit breakers, magnetic circuit breakers,
thermal-magnetic circuit breakers, and solid-state switches. Beginnings Overcurrents and circuit protectors
are not new subjects. Soon after Volta constructed his first electrochemical
cell, or Faraday spun his first disk generator, someone else graciously
supplied these inventors with their first short circuit loads. Patents on
mechanical circuit breaker devices go back to the late 1800's, and the concept
of a fuse goes all the way back to the first undersized wire that connected a
generator to a load.
In a practical sense, we can
say that no advance in electrical science can proceed without a corresponding
advance in protection science. An electric utility company would never connect
a new generator, a new transformer, or a new electrical load to a circuit that
cannot automatically open by means of a circuit protector. Similarly, a design
engineer should never design a new electronic power supply that does not
automatically protect its solid-state power components in case of a shorted
output. Protection from
overcurrent damage must be inherent to any new development in electrical
apparatus. Anything less leaves
the apparatus or circuit susceptible to damage or total destruction within a
relatively short time. Typical System Example Examples of overcurrent
protection devices are many: fuses, electromechanical circuit breakers and
supplementary protectors, and solid-state power switches. They are utilized in every conceivable electrical
system where there is the possibility of overcurrent damage. As a simple
example, consider the typical industrial laboratory electrical system shown in Figure
1.1. 
Figure 1.1One Line Diagram of a Typical Industrial
Laboratory System
Figure 1.1 is a one-line
diagram of the radial distribution of electrical energy, starting from the
utility distribution substation, going through the industrial plant and ending
in a small, laboratory personal computer. The system is said to be radial since
all branch circuits, including the utility branch circuits, radiate from
central tie points. There is only a single feed line for each circuit. There
are other network type distribution systems for utilities, where some feed
lines are paralleled. But the radial system is the most common and the simplest
to protect. Overcurrent protection is
seen to be a series connection of cascading current-interrupting devices. Starting
from the load end, we have a dual-element, or slow-blow fuse at the input of
the power supply to the personal computer. This fuse will open the 120-volt
circuit for any large fault within the computer. The large inrush current that
occurs for a very short time when the computer is first turned on, is masked by
the slow element within the fuse. Very large fault currents are detected and
cleared by the fast element within the fuse. Protection against excess
load at the plug strip is provided by the thermal circuit breaker within the
plug strip. The thermal circuit breaker depends on differential expansion of
dissimilar metals, which forces the mechanical opening of electrical contacts. The 120-volt single-phase
branch circuit, within the laboratory that supplies the plug strip, has its own
branch breaker in the laboratory's main breaker box or panel board. This branch circuit breaker is a
combination thermal and magnetic (or thermal-mag) breaker. It has a
bi-metallic element which, when heated by an overcurrent, will trip the device.
It also has a magnetic-assist winding which, by a solenoid type effect, speeds
the response under heavy fault currents. All of the branch circuits
on a given phase of the laboratory's 3-phase system join within the main breaker
box and pass through the main circuit breaker of that phase, which is also a
thermal-magnetic unit. This main circuit breaker is purely for back-up
protection. If, for any reason, a branch circuit breaker fails to interrupt
overcurrents on that particular phase within the laboratory wiring, the main
circuit breaker will open a short time after the branch circuit breaker should
have opened. Back up is an important
function in overload protection. In a purely radial system, such as the
laboratory system of Figure 1.1, we can easily see the cascade action in which
each overcurrent protection device backs up the devices downstream from it. If
the computer power supply fuse fails to function properly, then the plug strip
thermal circuit breaker will respond, after a certain coordination delay. If it
should also fail, then the branch circuit breaker should back them both up,
again after a certain coordination delay. This coordination delay is needed by
any back-up device to give the primary protection devicethe device that is
electrically closest to the overload or faulta chance to respond first. The
coordination delay is the principal means by which a back-up system is
selective in its protection. Selectivity is the property
of a protection system by which only the minimum amount of system functions are
disconnected in order to alleviate an overcurrent situation. A power delivery
system that is selectively protected will be far more reliable than one that is
not. For example, in the
laboratory system of Figure 1.1, a short within the computer power cord should
be attended to only by the thermal circuit breaker in the plug strip. All other
loads on the branch circuit, as well as the remaining loads within the
laboratory, should continue to be served. Even if the supplementary protector
within the plug strip fails to respond to the fault within the computer power
cord, and the branch circuit breaker in the main breaker box is forced into
interruptive action, only that particular branch circuit is de-energized. Loads
on the other branch circuits within the laboratory still continue to be served.
In order for a fault within the computer power cord to cause a total blackout
within the laboratory, two series-connected circuit breakers would have to fail
simultaneouslythe probability of which is extremely small. Trip Curves
The ability of a particular
circuit protector device to interrupt a given level of overcurrent depends on
the device sensitivity. In general, all overcurrent circuit protectors, no
matter the type or principles of operation, respond faster when the levels of
overcurrent are higher. Coordination of overcurrent
protection requires that application engineers have detailed knowledge of the
total range of response for particular protection devices. This information is
contained in the "trip time vs. current curves," commonly referred to
as the trip curves. A trip time-current curve displays the range of, and the
times of response for, the currents for which the device will interrupt current
flow at a given level of circuit voltage. For example, the time-current curves for
the circuit protectors in our laboratory example are shown superimposed in Figure
1.2. The rated current for a
device is the highest steady-state current level at which the device will not
trip for a given ambient temperature. The steady-state trip current is referred
to as the ultimate trip current. The ratings for the dual-element fuse in the
computer power supply, the plug strip thermal circuit breaker, the branch
circuit thermal-magnetic breaker and the main circuit thermal-magnetic breaker
are 2, 15, 20 and 100 amps, respectively. Note that, except for the fuse curve,
each time-current curve is shown as a shaded area, representing the range of
response for each device. Manufacturing tolerances and material property
inconsistencies are responsible for these banded sets of responses. Trip
time-current information for small fuses is usually represented in a
single-value average melting time curve. Figure 1.2 Trip Curves for the
Protection Devices in the Industrial Laboratory Example Even with a finite width to
the time-current curves, we can easily see the selectivity/coordination between
the different circuit protectors. For any given steady-state level of
overcurrent, we read up the trip time-current plot, at that level of current,
to determine the order of response. Consider the following three
examples for the laboratory wiring, plug strip, and computer system. Example 1: Component failure within the computer power supply Assume that a power
component within the computer power supply has failedsay two legs of the
bridge power rectifierand that the resulting fault current within the supply,
limited by a surge resistor, is 70 amps. We see from the fuse trip
curve that it should clear this level of current in approximately 20
milliseconds. If the fuse fails to interrupt the currentor worse, if the fuse
has been replaced with a permanent short circuit by a gambling repair personthe
thermal breaker in the plug strip should open the circuit within 0.6 to 3.5
seconds. The branch thermal-magnetic breaker will open the entire branch
circuit within 3.5 to 7.0 seconds, should the plug strip thermal circuit
breaker also fail to respond. Note that no back up is
provided for this particular fault after the branch circuit breaker. The main
laboratory 100-amp thermal-magnetic unit would respond only if the other loads
within the entire laboratory totaled greater than 30 amps at the time of the 70
amp power supply fault. Example 2: Plug
strip overload Assume that the computer
operator has spilled a drink, and to dry up the mess plugs two 1500-watt hair
dryers into the plug strip. The operator then flips them both on
simultaneously, drawing a total plug strip load current of approximately 30
amps. From the thermal circuit
breaker trip curve, we see that the plug strip unit should clear this overload
within 5 to 30 seconds. If the thermal circuit breaker fails, then the branch
circuit thermal-magnetic breaker should open within 30 to 130 seconds. Note the similarity between
the trip curves of the plug strip thermal unit and the branch circuit
thermal-magnetic unit in the region of 100 amps and below. This is because, for
these levels of currents, the thermal portion of the detection mechanism within
the thermal-magnetic branch breaker is dominant. Example 3: Short
circuit within the computer power cord Assume a frayed line cord
finally shorts during some mechanical movement. Assume also that there is enough resistance within the
circuit plug strip, and line cord system to limit the resulting fault current
to 300 amps. This level of current is
2000% (20 times) of the rated current of the plug strip thermal circuit
breaker, and is beyond the normal range of published trip time specifications
for thermal breakers (100% to 1000% of the rated current). Thus the exact trip
time range of the thermal unit is indeterminate. At high levels of fault
current, greater than 150 amps in this case, we can see the inherent speed
advantage of magnetic detection of overcurrents. This is evidenced by the fact
that the response curve for the thermal-magnetic branch circuit breaker knees
downward sharply at current levels between 150 and 200 amps. At these and
higher currents, the magnetic detection mechanism within the thermal-magnetic
unit is dominant. The response curve for the unit crosses over the plug
strip thermal circuit breaker response curve (assuming that it extends past its
1000% limit), and coordination between the two interrupters is lost. The range of response for the
thermal-magnetic breaker at 300 amps is 8 to 185 milliseconds. Should both the plug strip circuit breaker
and the branch circuit breaker fail to operate, the main laboratory breaker
should clear the fault within 11 to 40 seconds.
>> Next: Article 1.2
The Physics of Circuit Interruption
|